Dry-type transformers rely on solid insulation systems instead of liquid-filled tanks. Two widely used insulation processes are resin casting (epoxy potting / resin cast) and VPI (vacuum pressure impregnation / vacuum impregnation). Both improve dielectric strength and mechanical stability, but they differ in technique, performance, and best-use scenarios.
Liquid epoxy is poured or injected to fully encapsulate windings and gaps. The resin cures to form a rigid, protective shell around coils and components.
The winding assembly is placed in a vacuum chamber, air and trapped gases are removed, then liquid insulating resin is introduced (often under vacuum followed by pressure) so the resin penetrates every void. The part is then cured to harden the impregnation.
Insulation method: Resin cast dry transformer encapsulates externally and internally; VPI forces resin into internal voids under vacuum/pressure.
Void filling: VPI excels at filling microscopic voids and voids inside coils; resin cast may leave microscopic pockets unless carefully controlled.
Mechanical robustness: VPI typically provides superior bonding between strands and better resistance to vibration and thermal cycling.
Surface encapsulation: Resin cast gives a uniform outer shell and can simplify final machining or mounting.
Shrinkage & stress: Epoxy casting can shrink during cure and create internal stresses; controlled VPI processes can minimize problematic shrinkage by improving resin distribution.
Production complexity & cost: Resin casting is often simpler and faster for some designs; VPI requires vacuum/pressure equipment and careful process control, increasing cost but improving quality for demanding uses.
Excellent external encapsulation and moisture resistance
Simpler tooling for some coil shapes
Good for custom shapes, potting of components, and harsh-environment sealing
Potential for internal voids or resin shrinkage if process control is weak
Mechanical strength can be lower than properly executed VPI in areas of internal bonding
Superior penetration into windings — fewer voids and higher dielectric reliability
Better mechanical bonding; more resistant to vibration and thermal cycling
Improved long-term insulation stability and lower risk of partial discharge
More complex and capital-intensive process (vacuum chambers, controlled curing)
Slightly longer production cycles and higher initial cost
High-reliability installations (data centers, critical infrastructure, transportation): Prefer VPI for its superior void filling, dielectric reliability, and mechanical strength.
Harsh outdoor or moisture-prone environments that need complete surface sealing: Resin cast can be ideal for external encapsulation and extra moisture protection.
Cost-sensitive or small-batch custom work: Resin casting often offers faster turnaround and lower tooling cost.
Hybrid approach: Some manufacturers combine both techniques (e.g., VPI for internal winding impregnation and additional resin potting at external interfaces) to get the benefits of both.
Q: Does VPI remove all voids?
A: No manufacturing process guarantees zero voids, but properly controlled VPI greatly reduces voids compared with many casting methods.
Q: Which method handles high vibration better?
A: VPI generally provides better internal bonding and therefore improved resistance to vibration and mechanical shock.
Q: Is one method better for thermal performance?
A: Thermal performance depends on resin type and stack design. VPI’s closer contact between resin and conductor can improve heat transfer in many designs.
Both resin cast and VPI are proven insulation solutions for dry-type transformers. The right choice depends on the transformer’s operating environment, reliability requirements, budget, and production scale. For the highest electrical reliability and mechanical strength choose VPI; for strong external sealing, simpler production, or specific form-factor needs choose resin cast—or combine both where appropriate.
Oil Immersed Distribution Transformer VS Dry Type Cast Resin Transformer
In oil-immersed distribution transformers, oil is used as a heat conductor, and heat is released through radiator fins. Since the mineral oil has a flash point of 160 to 180°C, oil-immersed transformers must be installed in separate locations to prevent fire hazards in public spaces.
Aug. 25, 2025
Cast Resin Transformer: Definition, Types, Benefits, Applications, Maintenance
A cast resin dry-type transformer, also known as an epoxy cast resin dry-type transformer, is widely used due to its epoxy resin construction. Its windings are encased in high-quality protective material, ensuring robust insulation even in challenging environments with dust and humidity.
Aug. 22, 2025